Welcome to official website of Shandong Taikai High Voltage Switchgear Co.,Ltd.

Your present location:Home >> Products >> Taikai high voltage >> Products >> ZF16-252(L)/T4000-50 Gas Insulated Metal-enclosed Switchgear
PRODUCTSproducts center
PRODUCTS SEARCH
  • keyword :
  • Category :
  •  
  • product name: ZF16-252(L)/T4000-50 Gas Insulated Metal-enclosed Switchgear
  • Product number: b1015
  • Added time: 2016-03-18
  • Views : 210

1)Description:

   ZF16-252 is a compact metal-enclosed switchgear that consists of circuit breakers, disconnectors,

   earthing switches, current transformers, voltage transformers, busbars, bushings, and etc. 

   SF6 gas is used as insulation media to ensure safety. It is designed for 50 Hz, 252kV power 

   system projects where space is limited, such as extensions, in cities, industrial plants.

   Main busbar uses three-phase-enclosed type, and other components are three phase partition enclosed type.

   According to different control and protection method, it can be divided into intelligent type GIS 

   and traditional control and protection type GIS.    

2)Applications:

   Line, transformer, reactor and capacitor switching

   Point-on-wave switching

   High seismic applications

   High altitude applications

3)Why TAIKAI:

   ① TaiKai circuit breakers are widely used in industries such as power grid,

        power plant, petroleum, chemical, rail way, alternative energy, and etc.

   ② Exported into more than 40 countries;short delivery time supported by the fact 

        that 95% components are self-made with high standard 

   ③ professional service team to provide excellent customer service experience

   ④ mechanical endurance of 10000 operations

4)Technical Specification

   Installation condition:indoor/outdoor

   Ambient temperature:-40~+40℃

   Altitude: 0~4000m

   Rated Voltage:252kV

   Rated Current:2000~4000(three-phase enclosed 5000(single-phase enclosed

   Rated Frequency:50Hz

   Rated Short-time power frequency withstand voltage:across open contacts 460(+145)kV 

                                                        to earth 460kV  

   Rated lightning impulse withstand voltage:across open contacts1050(+100)kV 

                                                            to earth 1050kV 

   PD Level:≤5pC

   Rated peak withstand current:125kA

   Rated short-time withstand current:50kA

   Rated short-circuit duration:3s 

   Circuit breaker mechanical endurance:M2 class

   Disconnectors and earthing switches mechanical endurance:     M2 class

   Electrical Endurance: E2 class 

   Capacitive current breaking capacity:C2 class

Key words :